A gas cartridge type of fire extinguisher is a portable fire fighting device that operates using a gas cartridge or cylinder to expel the extinguishing agent when activated. Unlike the more common stored pressure fire extinguishers which store both the extinguishing agent and the propellant under pressure in a single container, cartridge-operated fire extinguishers separate the two components. These fire extinguishers are designed for specific applications and are often used in environments where there is a need for a longer discharge range or when a higher discharge pressure is required. They are commonly found in industrial settings, on construction sites and in areas where there may be a risk of larger fires. The operation of a gas cartridge fire extinguisher typically involves pulling the safety pin, squeezing the operating lever and activating the puncturing mechanism to release the gas which in turn expels the extinguishing agent. The expelled agent is then directed toward the fire to suppress it.
Specifications | 10 kg |
Working Temperature °C | -30 °C to +60 °C |
Burst Pressure | 55/80 bar min., 110 bar (actual) approx |
Cylinder Testing Pressure | 35 bar for 30 sec. |
Min. Effective Discharge Time | 13 sec. |
CO2 Gas Cartridge | 180 gms. |
Charge | Dry Chemical Powder (TEC) |
Applicator | Specially designed Cast Aluminium nozzle with radial fins internally |
Specifications | 4 kg | 6 kg | 9 kg | |
Fire Rating | 89B | 144B | 233B | |
Working Temperature °C | -30 °C to +60 °C | |||
Burst Pressure | 55/80 bar min., 110 bar (actual) approx | |||
Cylinder Testing Pressure | 35 bar for 30 sec. | |||
Min. Effective Discharge Time | 13 sec. | 15 sec. | ||
CO2 Gas Cartridge | 120 gms. | 180 gms. | ||
Charge | Sodium Bi-Carbonate |
Specifications | 4 kg | 6 kg | 9 kg |
Fire Rating - MAP 50 | 3A 55B | 3A 89B | 6A 144B |
Fire Rating - MAP 90 | 3A 89B | 4A 144B | 6A 233B |
Working Temperature °C | -30 °C to +60 °C | ||
Burst Pressure | 55/80 bar min., 110 bar (actual) approx | ||
Cylinder Testing Pressure | 35 bar for 30 sec. | ||
Min. Effective Discharge Time | 13 sec. | 15 sec. | |
CO2 Gas Cartridge | 120 gms. | 180 gms. | |
Charge | ABC Dry Powder (MAP50 / MAP90) |
Specifications | 9 ltr. |
Fire Rating | 6A |
Working Temperature °C | +5 °C to +60 °C |
Burst Pressure | 55/80 bar min., 110 bar (actual) approx |
Cylinder Testing Pressure | 35 bar for 30 sec. |
Min. Effective Discharge Time | 15 sec. |
CO2 Gas Cartridge | 60 gms. |
Charge | vWater with Additive |
Specifications | 9 ltr. |
Fire Rating | 6A 144B |
Working Temperature °C | +5 °C to +60 °C |
Burst Pressure | 55/80 bar min., 110 bar (actual) approx |
Cylinder Testing Pressure | 35 bar for 30 sec. |
Min. Effective Discharge Time | 15 sec. |
CO2 Gas Cartridge | 60 gms. |
Charge | Water with AFFF 6% |
Specifications | 9 ltr. |
Fire Rating | 6A 144B |
Working Temperature °C | +5 °C to +60 °C |
Burst Pressure | 55/80 bar min., 110 bar (actual) approx |
Cylinder Testing Pressure | 35 bar for 30 sec. |
Min. Effective Discharge Time | 15 sec. |
CO2 Gas Cartridge | 60 gms. |
Charge | Water with AR-AFFF 6X6% |